Specifications:
Product Name | Combination Safety Shower |
Model | WG7053FG, WG7053F, WG7053FY |
Standard | ANSI Z358.1, AS 4775, CSA, CE |
Material | 304 stainless steel, AES (Acrylonitrile-ethylene-styrene) Plastic |
Flow Rate ( L/min )-Eye/Face Wash | 11.4 |
Flow Rate ( L/min )-Shower | 75.7 |
Water Bowl (D*H/cm: 32*9.5 )-AES plastic | NO |
Water Bowl (D*H/cm: 32*9.5 )-304 SS | YES |
Shower (D*H/cm: 25.5*7.5)-AES plastic | NO |
Water Bowl (D*H/cm: 25.5*7.5 )-304 SS | YES |
Valve 1/2″ | YES |
Valve 1″ | YES |
Inlet | 1″ |
Outlet | 1″ |
Pressure Kpa | 210 |
Features:
- High Quality & High Performance: AES plastic has weather resistance properties and applies to indoors or outdoors; With good acid proof, alkali prevention performances, 304 SS is ideal for harsh environment, complying with ANSI Z358.1-2014. Eye wash station can be installed outdoors or indoors, can be effectively used 0.3 million times.
- Eye & Face Washing Station: The spray heads have a built-in filter to filter impurities in the water, providing a comfortable stream and hand free operation condition, which make sure 15 min safety eye washing time to protect hurt eye during emergency.
- Emergency Shower: When shower is needed, pull down the shower rod with triangular handle, then emergency shower can be gotten. The shower head delivers a large volume flushing fluid spread evenly in a precise pattern and controlled flow rate. This emergency shower station was suitable for place where water pipe is available.
- Compact Design: The equal length of main pipes makes packaging more compact so that helps to save space and cost; Equiped with flat washer in quick coupling to prevent leakage between joints and fitting.
Combination Unit:
- Valve mechanism activates in one second or less; It stays open until manually closed.(Section 4.2,5.2,6.1.4,6,2)
- Be connected to a system capable supplying adequate flushing fluid when all components are oprated simultaneously,(Section 4.5.5,7.4.4)
- Height of the flushing fluid column pattem shall be between 82″(208.3cm) and 96″(243.8cm) above floor. (Section 4.1.3,4.5.4)
- Watersupply shall be sufficient to supply at least 20GPM (75.7LPM) for 15 mimutes. (section 4.1.2,4.5.5)
- Valve actuator shall be located not more than 175.3cm (69″) above floor. (section 4.2)
- The diameter shall be minimum of 50.8cm (20″) at 152.4cm (60″) above floor. (section 4.1.4)
- Center of the flushing fluid patterm shall be at least 16″(40.6cm) from any obstruction.(Section4.1.4,4.5.4)
- Water flow pattren shall be positioned between 33″(83.8cm) and 53″(134.6cm) from the level on which user stands and 6″(15.3cm) minimum from the wall or nearest obstruction.(Section 5.4.4,6.4.4)
- Deliverd at least 3.0 gallons(11.4liters) of water per minute for 15-minute (Section 6.1.6,6.4.5)
- Construted of materials that will not corrode in the presence of the flushing fluid (Section 7.1.1,7.1.2,7.1.3)
- Located 10 seconds or 55 feet from contaminants or hazardous materials, Locate on the same level as hazad and free of obstructions.(Section 7.4.2,B5)
- Protect nozzle head from airborne contamination, dust covers shall be removed by water flow immedlately (Section 5.1.3,6.1.3)
- Provided fushing fluid to both eye and face simultaneously at a velocity low enough without injury to skin (Section 5.1.1.6.1.1)